Thermon BSX 5-2 – Self-Regulating Heat Trace Cables
Thermon BSX 5-2 trace heating cables are specified to provide frost protection and process temperature maintenance up to 65° Celsius : suitable for trace heating pipes, drums, process skids, valves, flexible hoses and vessels.
Thermon BSX 5-2 heating cables provide a power output of 5 watts per metre (15 watts per foot) at 50°F (10°C) and are available in both 120 Volt and 240 Volt service voltage options. Order Thermon BSX 5-1 for 120 Volt heat trace cables.
THERMON BSX 5-2 HEAT TRACING CABLES – POWER OUTPUT CURVES & CIRCUIT BREAKER SIZING

Thermon BSX 5-2 Heat Tracing Cables
| 240 Vac Service Voltage | Maximum Circuit Length³ vs. Breaker Size ft (m) | |||
| Thermon Order Code | Start-Up Temperature ºF (ºC) | 20A | 30A | 40A |
| BSX 5-2 | 50 (10) | 480 (146) | 600 (183) | 600 (183) |
| 0 (-18) | 395 (120) | 590 (180) | 600 (183) | |
| -20 (-29) | 350 (107) | 525 (160) | 590 (180) | |
| -40 (-40) | 315 (96) | 475 (145) | 530 (162) |
HEAT TRACE APPLICATION – DELUGE SKIDS PROCESS TEMPERATURE MAINTENANCE
Deluge skids are process packages used to control the flow of water or water/foam solution in fixed fire suppression, cooling or gas containment systems.
THERMON BSX 5-2 HEAT TRACING CABLES – CABLE JACKETS
Standard polyolefin heating cable overjacket (Thermon OJ) provides cable and braid protection for exposure to aqueous inorganic chemicals. Thermon FOJ fluoropolymer trace heater cable overjacket provides enhanced protection against corrosive and aggressive organic chemicals. Both heat trace cable options are ATEX and IECEx Certified for installation in Zone 1 and Zone hazardous areas.